Calculation of Required Cells for An AHU

Air Velocity = Face Area x Air Flow
- Air Velocity in cubic meter / hour
- Face area of AHU in square meter
-Air flow in meter / hour

Example:

Air Velocity of AHU = 26200 CMH
Electronic Cells Quantity = 18 pieces
Effective Area / Cell = (Cell Height x Cell Width)
= 0.500 x 0.314 = 0.157 square meter
Effective Area of 18 Cells = 0.157 x 18 = 2.826 square meters
Air Flow = (Air Velocity + Face Area) = (26,200÷2.826)
= 9271 M/hr (2.57 M/s)


How to Find Out The Required Number of Cells?

1. See your air flow (CMH) for your air handling unit.
2. Draw a horizontal line from your air flow to air velocity line.
3. Draw a vertical line from intersection point to required cells line.
The number you meet is the cells quantity required for your AHU at 2.5 M/s Air Velocity.

Different Electronic Cells Quantity for Different Air Velocity


Required Bravo Models for 2.5M/s Air Velocity
Air
Volume
CMH
Model
Length x Height x Depth
Cell Qty Layer
Supply VAC

Power
Pack
Qty

Power Consumption
17,000
DT12-2S
1894 x 1224 x 175
12
2
230VAC/ 50Hz
6
180 Watts
20,000
DT14-2S
2209 x 1224 x 175
14
2
230VAC/ 50 Hz
7
210 Watts
22,600
DT16-2S
2523 x 1224 x 175
16
2
230VAC/ 50 Hz
8
240 Watts
25,000
DT18-3S
1894 X 1836 X 175
18
3
230VAC/ 50 Hz
9
270 Watts
30,000
DT21-3S
2209 X 1836 X 175
21
3
230VAC/ 50 Hz
11
330 Watts
34,000
DT24-3S
2523 X 1836 X 175
24
3
230VAC/ 50 Hz
12
360 Watts
38,000
DT27-3S
2838 X 2448 X 175
27
3
230VAC/ 50 Hz
14
420 Watts
45,000
DT32-3S
2523 X 2448 X 175
32
4
230VAC/ 50 Hz
16
480 Watts
51,000
DT36-4S
2838 X 2448 X 175
36
4
230VAC/ 50 Hz
18
480 Watts
56,500
DT40-4S
3153 X 2448 X 175
40
4
230VAC/ 50 Hz
20
600 Watts
68,000
DT48-4S
3748 X 2448 X 175
48
4
230VAC/ 50 Hz
24
720 Watts